Delta GR150 Instrucciones de operaciones Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 24
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
Page 10
1285-00
60708-153
INSTALLATION NOTES
Because of the many different types of service, feeder, and
distribution equipment, no specific wiring instructions can be
provided. It is recommended that only copper wire be used. In
all cases it is essential that while the load is connected to the
generator, there can be absolutely no feedback from the genera-
tor to the power line or the power line to the generator. When
properly installed, the normal A.T.S. Control and safety systems
will eliminate all paths for feedback.
To wire the automatic transfer switch into the existing wiring, first
determine which circuits will be on the emergency load circuit. If
the entire load is to be transferred, the transfer switch can be
wired in directly after the watt-hour meter and the service en-
trance, providing the service entrance ampere rating is within the
transfer switch’s rated capability.
If only specific circuits are to be powered under emergency power
failure conditions, an additional distribution panel designated
“emergency distribution panel” must be installed.
All selected emergency circuits are removed from main distribu-
tion panels and installed in the emergency distribution panel. The
A.T.S. is then installed between the main panel and the emer-
gency distribution panel. Suggested circuits: freezer, refrigerator,
furnace, emergency lights, sump pump, emergency outlet circuits,
etc. Total running load must not exceed generator rating.
A.C. ELECTRICAL
CONNECTIONS
NOTICE - CLASS 1 WIRING METHODS ARE TO BE USED FOR
ALL FIELD WIRING CONNECTIONS TO TERMINALS OF A
CLASS 2 CIRCUIT
Note: This symbol always indicates ground where
shown.
All wiring must be completed in accordance with the Nation
Electric Code as well as any state or local codes.
You must pay particular attention to wire size requirement for the
amperage of service you are dealing with. Appendix "1" provides
you guidance on wire sizing based on both wire type and amper-
age. Wire amperage's have been derated for 40
o
C ambient
temperatures operation.
A - Neutral Lugs, These neutral lugs are isolated from ground
and provided for you to connect your neutral wire from the
transfer switch to the generator.
Refer to the neutral lugs installed in your connection box for wire
sizing and proper torques specifications. If you have additional
question on wiring sizing contact the WINPOWER Service
department at 507-357-6707.
B - Generator Circuit Breaker, This circuit breaker provides
overload protection for the generator. Your power feeds from the
transfer switch will connect to the bottom lugs on the circuit
breaker. The generator power feeds have already been wired
into the upper lugs.
Please refer to the circuit breaker installed on your unit for
breaker lug capacities and proper torque specifications.
To select the proper conductor size between the Generator and
the ATS, first look at the amperage rating of the circuit breaker
and then refer to Appendix "1" for guidance on wire sizing based
on both wire type and amperage. Wire amperages have been
derated for 40
o
C ambient temperatures operation.
For additional information on wire sizing refer to table 310-16 of
the National Electrical Code ANSI/NFPA 70.
C - Ground Lug, These ground lugs are bonded to ground and
are provided for you to connect your ground wire from the transfer
switch to. Refer to the ground lugs installed in your connection
box for wire sizing and proper torques specifications. If you have
additional question on wiring sizing contact the WINPOWER
Service department at 507-357-6707.
D - 120 VOLT GFCI CIRCUIT TERMINAL BLOCK - These
terminals are rated for 85 amps and will handle wire sizes #4
AWG to #18 AWG. They should be torqued to 16 in. lbs. This
circuit must be fed from a fused circuit in the distribution panel
and provides power for the blockheater and the battery charger.
G - This lug is provided on the neutral terminal block to allow you
to run a neutral to ground lead if you are using the generator in a
stand alone application. This would be an application where
there is not a distribution panel and no other ground to neutral
bond in the wiring system. If a grounding wire is attached here
remove the floating neutral label in the panel. This will not be
used when you are wiring a generator and transfer switch
into an existing power system.
Vista de pagina 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 23 24

Comentarios a estos manuales

Sin comentarios