
D
Display Possible cause/Suggested solution
Motor Thermistor The motor thermistor input has been enabled and:
The resistance at the thermistor input has exceeded 3.6 k˖ for more than one second.
The motor winding has overheated. Identify the cause of the overheating and allow the motor to
cool before restarting.
The motor thermistor input has been open.
NOTE
If a valid motor thermistor is no longer used, a 1.2 k˖ resistor must be fitted across
terminals 05, 0
6.
Related Pars.: 16-9
Network Comms The network master has sent a trip command to the starter, or there may be a network communi-
cation problem.
Check the network for causes of communication inactivity.
Related Pars.: 16-11
Parameter out of Range -
A parameter value is outside the valid range.
The starter will load the default value for all affected parameters. Press M
to go to the first
invalid parameter and adjust the setting.
Related Pars.: None
Phase Sequence The phase sequence on the soft starter's input terminals (L1, L2, L3) is not valid.
Check the phase sequence on L1, L2, L3 and ensure the setting in Par. 2-1 is suitable for the instal-
lation.
Related Pars.: 2-1
Power Loss The starter is not receiving mains supply on one or more phases when a Start Command is given.
Check that the main contactor closes when a start command is given, and remains closed until the
end of a soft stop.
Related Pars.: 15-5
Starter/Comms -
There is a problem with the connection between the soft starter and the optional communications
module. Remove and reinstall the module. If the problem persists, contact your local distributor.
There is an internal communications error within the soft starter. Contact your local distributor.
Related Pars.: 16-10
Thermistor Cct The thermistor input has been enabled and:
The resistance at the input has fallen below 20 ˖ (the cold resistance of most thermistors will be
over this value) or
A short circuit has occurred. Check and resolve this condition.
Check that a PT100 (RTD) is not connected to 05, 06.
Related Pars.: None.
Time - Overcurrent The MCD 500 is internally bypassed and has drawn high current during running. (The 10A protection
curve trip has been reached or the motor current has risen to 600% of the motor FLC setting.)
Related Pars.: None
Undercurrent The motor has experienced a sharp drop in current, caused by loss of load. Causes can include broken
components (shafts, belts or couplings), or a pump running dry.
Related Pars.: 2-4, 2-5, 16-3
Unsupported Option The selected function is not available (e.g. jog is not supported in inside delta configuration).
Related Pars.: None
Troubleshooting MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®
is a registered Danfoss trademark 67
Comentarios a estos manuales