N
NOTE
AAC Adaptive Acceleration Control will control the load
according to the programmed profile. Start cur
rent will vary
according to the selected acceleration profile and the
programmed start time.
If replacin
g a motor connected to an MCD 500 programmed
for AAC Adaptive Control starting or stopping, or if the
s
tarter has been tested on a different motor prior to actual
installation, the starter will need to lea
rn the characteristics
of the new motor. The MCD 500 will automatically re-learn
the motor's characteri
stics if Par. 1-1 Motor Full Load Current
or Par. 1-12 Adaptive Control Gain is changed.
5.3.4 Kickstart
Kickstart provides a short boost of extra torque at the
beginning of a start, and can be used in conjunction with
current ramp or constant current starting.
Kickstart can be useful to help start loads that require high
breakaway torque but then accelerate easily (for example
flywheel loads such as presses).
700%
600%
500%
300%
100%
400%
200%
10% 20% 30% 40% 50%
Rotor speed (% full speed)
60% 70% 80% 90% 100%
177HA508.10
Current (% motor full load current)
1
5
4
6
3
2
1: Kickstart level (Par. 1-7)
2: Kickstart time (Par. 1-8)
3: Initial current (Par. 1-5)
4: Start ramp time (Par. 1-6)
5: Current limit (Par. 1-4)
6: Full voltage current
5.4 Stopping Modes
5.4.1 Coast to Stop
Coast to stop lets the motor slow at its natural rate, with no
control from the soft starter. The time required to stop will
depend on the type of load.
5.4.2 TVR Soft Stop
Timed voltage ramp reduces the voltage to the motor
gradually over a defined time. The load may continue to run
after the stop ramp is complete.
Timed voltage ramp stopping can be useful for applications
where the stop time needs to be extended, or to avoid
transients on generator set supplies.
70%
60%
50%
30%
10%
40%
Time
Voltage (% full voltage)
20%
80%
90%
100%
177HA509.10
1
1: Stop time (Par. 1-11)
5.4.3 AAC Adaptive Acceleration Control
To use AAC Adaptive Acceleration Control to control
stopping performance:
1. Select Adaptive Control from the Stop Mode menu
(Par. 1-10)
2. Set the desired Stop Time (Par. 1-11)
3. Select the required Adaptive Stop Profile (Par. 1-14)
Application Examples MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®
is a registered Danfoss trademark 31