27610 – Current Transformer
Basic Form Information
The PF Current Transformer form is used for power/dissipation factor testing
high voltage current transformers, those generally rated over 5kV. Power factor
testing is normally not conducted on doughnut style current transformers.
Nameplate information (serial number, ratings, etc.) should be entered which
identifies the asset being tested, and general information regarding the test
conditions (test date, weather conditions, etc.) should also be noted.
Labeling of windings and bushings vary from country to country and may also
vary within a country based on manufacturing year and more. All description
uses labeling H1, H2, H3, H0 for High side bushings. Equivalent labeling used
are e.g. 1U, 1V, 1W, 1N or A, B, C, N. Corresponding labeling for other
windings are e.g. X1, X2, X3, X0; 1U, 2V, 2W, 2N; a, b, c, n respectively Y1, Y2,
Y3, Y0, 3U, 3V, 3W, 3N.