Chapter 5 Communication Interface
19
SMART Slot
This SMART slot is for mini-size cards. You can install the Mini SNMP, Mini Relay I/O, Mini USB, Mini
ModBus, or Mini TVSS card in this slot to give the system network communication, dry contact, USB
communication, ModBus communication, and surge protection functions respectively. Please see Figure
5-d & 5-e
.
(Figure 5-d) 5kVA/ 6kVA
(Figure 5-e) 10kVA
External Battery Pack Connector
This connector is for connection to an external battery pack. Please see below for relevant information.
z
Battery:
1. Charge Voltage:
1) 5kVA/ 6kVA: 217.6Vdc
2) 10kVA: 272.0Vdc
2. Charge Current:
1) 5kVA/ 6kVA: 0.7A (default)
2) 10kVA: 1.5A (default)
NOTE: Please note that RS232 port will disable if you insert a mini-size card in the SMART slot.