Delta AH500 series Manual Pagina 93

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 297
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 92
AH500 Hardware Manual
Functional specifications
Analog-to-digital
conversion
Centigrade (°C) Fahrenheit (°F) Input impedance
Rated input range
Pt100: -180°C~800°C
Ni100: -80°C~170°C
Pt1000: -180°C~800°C
Ni1000: -80°C~170°C
Pt100: -292°F~1,472°F
Ni100: -112°F~338°F
Pt1000: -292°F~1,472°F
Ni1000: -112°F~338°F
0~300
Average function Range: 1~100
Self-diagnosis Disconnection detection
AH08PTG-5A
Electrical specifications
Number of analog
inputs
8
Three-wire configuration: Pt100/Ni100/Pt1000/Ni1000 sensor, and 0~300
input impedance
Applicable sensor
Two-wire/Four-wire configuration: Pt100/Ni100/Pt1000/Ni1000 sensor, and
0~300 input impedance
Pt100: DIN 43760-1980 JIS C1604-1989; 100 3850 PPM/°C
Pt1000: DIN EN60751; 1 k 3850 PPM/°C
Ni100/Ni1000: DIN 43760
Supply voltage 24 V DC (20.4 V DC~28.8 V DC) (-15%~+20%)
Connector type Removable terminal block
The error is ±1°C of a Pt100/Pt1000/Ni1
00/Ni1000 sensors temperature.
Overall accuracy
The error is ±0.1% of a resistance in the range of 0 to 300 .
Conversion time
Quick mode:
Four-wire/Two-wire configuration: 20 ms/channel
Three-wire configuration: 200 ms/channel
General mode: A conversion time will be gotten after the conversion time of
the two channels in a group is added up.
Four-wire/Two-wire configuration: 200 ms/channel
Three-wire configuration: 400 ms/channel
Isolation
An analog circuit is isolated from a digital circuit by a digital integrated circuit,
and the analog channels are isolated from one another by optocouplers.
Isolation between a digital circuit and a ground: 500 V DC
Isolation between an analog circuit and a ground: 500 V DC
Isolation between an analog circuit and a digital circuit: 500 V DC
Isolation between two group circuits: 500 V DC
Isolation between the 24 V DC and a ground: 500 V DC
Functional specifications
Analog-to-digital
conversion
Centigrade (°C) Fahrenheit (°F) Input impedance
Rated input range
Pt100: -180°C~800°C
Ni100: -80°C~170°C
Pt1000: -180°C~800°C
Ni1000: -80°C~170°C
Pt100: -292°F~1,472°F
Ni100: -112°F~338°F
Pt1000: -292°F~1,472°F
Ni1000: -112°F~338°F
0~300
Average function Range: 1~100
Self-diagnosis Disconnection detection
AH04TC-5A/AH08TC-5A
Electrical specifications
Module name AH04TC-5A AH08TC-5A
Number of analog
inputs
4 8
3-49